FIRE-WATER PLANNING
Use the WTR Fire worksheet
Enter your name and email to estimate fire-water storage for your property. Freedom Rainwater can help with the next steps.
Questions? Call 512-560-8412Find a likely fire service area by address, your location at the property, or a map pin. Confirm the reviewing AHJ directly.
?
Fire-water calculation worksheet
Follow the familiar footprint → volume → factors → gallons sequence.
?
?
?
?
?
?
3 · Severe: sawmills, flour mills, flammable-liquid spraying.
4 · High: commercial barns, warehouses, repair garages.
5 · Moderate: restaurants, machine shops, farm equipment sheds. Combustible storage cannot exceed 12 ft for this class.
6 · Low: churches, doctors’ offices. Dwellings are class 6 in 2027; parking garages are class 6 in 2022.
7 · Light: offices, schools. Dwellings are class 7 in 2022.
For mixed uses, the most hazardous applicable class (lowest number) governs the whole building. Contents can change the answer; choose “I don’t know” when unsure.
Choose Dwelling or Parking garage above to fill this class automatically. For other uses, select the documented class here; use “I don’t know” if it needs professional review.
?
Type I · 0.5: fire-resistive structure with qualifying noncombustible or limited-combustible structural elements and ratings.
Type II · 0.75: qualifying noncombustible structure; examples can include steel or concrete construction, depending on assembly and ratings.
Type III · 1.0: qualifying noncombustible exterior walls with some combustible interior framing; often called ordinary construction.
Type IV · 0.75: qualifying heavy timber with required member sizes and wall construction.
Type V · 1.5: wood-frame or other combustible structure, such as many frame buildings.
A brick veneer or metal siding alone does not establish a type. Confirm the structural assemblies and fire-resistance ratings from plans. Mixed construction uses the highest applicable factor. In 2022, a dwelling’s factor is capped at 1.0.
?
?
“In accordance with NFPA 1403, an additional water supply in the amount of 50% of total required fire flow must be available to handle unforeseen situations.”
?
Worksheet attribution only. Confirm whether your AHJ applies this additional reserve to this project; NFPA 1403 addresses live-fire training.
The sizing base is the Chapter 4 result, or the separately entered AHJ gallon amount. The optional reserve changes tank recommendations, not the Chapter 4 result or its delivery-rate lookup.
The calculated quantity is not the usable water guaranteed by a tank. Outlet height, draw-off, fittings and delivery need separate design review. Whole gallons are rounded up for planning; the AHJ must confirm the rounding convention.
Project and AHJ record
?
Fire tank builder
The builder shows the smallest XLE and smallest flat panel configuration that meet the worksheet target for your chosen tank count. Final usable volume depends on the outlet and site design.
Listed net usable capacities assume 6 in. below an anti-vortex plate and 6 in. of freeboard (manufacturer's low seismic risk basis). Confirm the actual outlet elevation, draw-off, seismic design, and available volume before acceptance. The worksheet's delivery rate must be achievable at the fire department connection.
| Choose | Model | Nominal gal / tank | Listed usable gal / tank* | Diameter × height | Concrete pad diameter | Capacity check |
|---|
Select a model to create the configuration schedule.
Base kit and design checks
Department choices and optional equipment
Select components only when confirmed by the fire department or the project designer. Select the hard suction hose and storage details requested by the fire department.
No pricing is published. The PDF is a concept package for review; it is not a final installed proposal or AHJ approval.
Records saved on this device
Local preview only: records are not shared with Freedom, a department, or another device. Export for backup. Admin authentication and shared database are not yet connected.
| Project | Contact | AHJ | Status | Saved |
|---|
Saved worksheets stay on this device only. Export a CSV if you need a backup or want to move records to another system.
Annual fire tank inspection
Track the due date for each fire tank, request a visit, and keep inspection reports and fire department submission records together.
Due dates follow the schedule recorded for your site. Freedom can confirm your department's requirements. A due date is separate from a confirmed appointment.
Open your inspection records
Verify your email to protect your property records and reports.
Open inspection records in a separate window
+ Register a fire tank for inspection tracking

Preliminary Fire-Water Storage Calculation Sheet
WTR Fire · Powered by Freedom Fire Tanks · For AHJ review, not approval
Department comments: _________________________________________________________________
Reviewer / date: _____________________________________________________________________
Conceptual and preliminary. The AHJ controls local criteria and acceptance. Drawings require site-specific engineering and review.